?> 50Hz 1640kW 2050kVA Perkins 4016TAG2A Diesel Generator

50Hz 1640kW 2500kVA Diesel Generator with Perkins 4016TAG2A Engine

50Hz 1640kW 2500kVA Diesel Generator with Perkins 4016TAG2A Engine - Image 1
  • 50Hz 1640kW 2500kVA Diesel Generator with Perkins 4016TAG2A Engine - Image 1
  • 50Hz 1640kW 2500kVA Diesel Generator with Perkins 4016TAG2A Engine - Image 2

Short Description

GENLITEC GPP2000D5/GPP2000S5 diesel generator set powered by original Perkins 4016TAG2A, with prime power 1600kW/2000kVA, standby power 1800kW/2250kVA.

  • ModelGPP2050S5
  • Prime Power (PRP)1640kW/2050kVA
  • Standby Power (ESP)1800kW/2250kVA
  • Engine4016TAG2A
  • Fuel consumption (100%)434L/H
Share

Product Details

Product Tags

50Hz 1640KW 2050KVA Diesel Generator with Perkins 4016TAG2A Diesel Engine

Introduction

The GENLITEC POWER GPP2050D5 / GPP2050S5 is a 2050 kVA diesel generator set designed for reliable prime, standby and backup power applications. With a rated output of 1640KW/2050KVA prime power and 1800KW/2250KVA standby power, this 50Hz diesel generator operates at 1500 RPM and provides dependable three-phase power for commercial, industrial, construction, agricultural, telecommunications and other demanding applications.

Powered by a Perkins 4016TAG2A diesel engine, the GPP2050D5 / GPP2050S5 features a 61.1L sixteen-cylinder V-type engine with turbocharged and air-to-air charge cooled induction, direct injection and electronic governing. The generator set is equipped with a 1664KW/2080KVA alternator and a standard 2000L fuel tank. The GPP2050D5 is supplied in open type configuration, while the GPP2050S5 is supplied as standard with a 40HQ containerized canopy for sound attenuation, weather protection and international transportation.

Generator Set

Open Type Model GPP2050D5
Silent Type Model GPP2050S5
Frequency 50Hz
Phase & Wires 3 Phase, 4 Wires
Power Factor 0.8
Prime Power 1640KW/2050KVA
Standby Power 1800KW/2250KVA
Rated Voltage 220/380V; 230/400V; 240/415V
Rated Speed 1500 RPM
Fuel Tank Capacity 2000L

Diesel Engine

Engine Model Perkins 4016TAG2A
Cylinder Number 16
Cylinder Arrangement 60° V-Type
Cycle 4 Stroke
Aspiration System Turbocharged and Air-to-Air Charge Cooled
Cooling Method Liquid Cooled
Governor Type Electronic
Bore x Stroke 160 x 190 mm
Compression Ratio 13.6:1
Rated Speed 1500 RPM
Displacement 61.1L
Engine Power - Prime 1766KW Gross / 1715KW Net
Engine Power - Standby 1937KW Gross / 1886KW Net
Combustion System Direct Injection
Coolant Capacity Approximately 316L
Oil Capacity Approximately 237L
Electric Starting System DC 24V

Fuel Consumption

Standby Power Rating 483L/H
100% Prime Load 434L/H
75% Prime Load 316L/H
50% Prime Load 210L/H

Alternator

Number of Phase 3
Rated Power 1664KW/2080KVA
Frequency 50Hz
Power Factor 0.8
Poles 4
Temperature Rise 125K
Terminals 6/12
Insulation Class H
Ambient Temperature 40℃
IP Rating IP23
Excitation System Self-Excited
Bearing Single Bearing
Coating Vacuum Impregnation
Voltage Regulator A.V.R
Coupling Flexible Disc

Control Panel

○ Emergency stop button ○ Main circuit breaker
○ Float battery charger ○ Manual/Auto start control panel
○ Fuel level meter ○ Controller power switch
○ Alarm buzzer

Sound Attenuated Enclosure

○ GPP2050S5 is supplied as standard with a 40HQ containerized canopy

○ Weatherproof sound-attenuated containerized enclosure with internal exhaust silencer

○ Corrosion-resistant construction suitable for outdoor installation

○ Suitable for international transportation and demanding outdoor applications

Options

○ ATS for automatic start and stop when utility power fails or returns

○ Synchronization System

○ Remote monitoring system

○ Water-Jacket Heater

○ Other Heaters

Applications

The GENLITEC POWER 1640KW/2050KVA diesel generator set is suitable for a wide range of prime, standby and backup power applications, including:

○ Commercial and office buildings

○ Industrial facilities

○ Construction and job sites

○ Agricultural and rural facilities

○ Telecommunication and remote sites

○ Emergency and standby power systems

Why Choose GENLITEC POWER

GENLITEC POWER GPP2050D5 / GPP2050S5 diesel generator sets combine the Perkins 4016TAG2A engine with a high-power configuration for dependable prime and standby power.

○ Perkins 4016TAG2A diesel engine for reliable high-power generation

○ 1640KW/2050KVA prime power and 1800KW/2250KVA standby power

○ 61.1L sixteen-cylinder V-type engine with turbocharged and air-to-air charge cooled induction

○ 1664KW/2080KVA alternator for high-power generator applications

○ Multiple voltage configurations available

○ Open type and 40HQ containerized canopy configurations available

○ Electronic engine governing for precise engine speed and performance management

○ Suitable for commercial, industrial and backup power applications

○ Factory-direct supply with customized generator set solutions

GENLITEC POWER® Why Choose GENLITEC POWER

Warranty

GENLITEC POWER provides a standard warranty of 12 months or 1000 working hours, whichever comes first. For details, please refer to the GENLITEC POWER® Warranty Policy.

FAQ

Q: What is the rated power of the GPP2050D5 / GPP2050S5 generator set?
A: The generator set provides 1640KW/2050KVA prime power and 1800KW/2250KVA standby power at 50Hz and 1500 RPM.
Q: Which diesel engine is used in the GPP2050D5 / GPP2050S5?
A: The generator set is powered by a Perkins 4016TAG2A sixteen-cylinder, 61.1L V-type diesel engine with turbocharged and air-to-air charge cooled induction, direct injection and electronic governing.
Q: What voltage configurations are available?
A: The available rated voltage configurations are 220/380V, 230/400V and 240/415V.
Q: What is the difference between the GPP2050D5 and GPP2050S5?
A: The GPP2050D5 is the open type model. The GPP2050S5 is supplied as standard with a 40HQ containerized canopy providing sound attenuation and weather protection.
Q: What is the fuel consumption of the GPP2050D5 / GPP2050S5?
A: The specified fuel consumption is approximately 483 L/H at standby power, 434 L/H at 100% prime load, 316 L/H at 75% prime load and 210 L/H at 50% prime load.
Q: What is the fuel tank capacity?
A: The standard fuel tank capacity is 2000L.
Q: What is the frequency and rated speed of the generator set?
A: The GPP2050D5 / GPP2050S5 operates at 50Hz with a rated engine speed of 1500 RPM.
Q: How many cylinders does the Perkins 4016TAG2A engine have?
A: The Perkins 4016TAG2A is a sixteen-cylinder 60° V-type diesel engine with a 61.1L displacement.
Q: What are the bore and stroke of the Perkins 4016TAG2A engine?
A: The engine has a bore of 160 mm and a stroke of 190 mm, with a compression ratio of 13.6:1.
Q: What is the engine oil and coolant capacity?
A: The engine oil capacity is approximately 237L and the coolant capacity is approximately 316L.
Q: What is the warranty period for the GPP2050D5 / GPP2050S5?
A: GENLITEC POWER provides a standard warranty of 12 months or 1000 working hours, whichever comes first.

  • Previous: 50Hz 728kW 910kVA Diesel Generator with Cummins KTA38-G2A Engine